VPP--DESIGN CRITERIA FOR AN INSTALLATION TO REMOVE HYDROGEN FLUORIDE AND FLUORINE FROM THE CELLS 1 AND 2 VENTILATION GASES PRIOR TO FILTRATION
Criteria are presented for a horizontal cocurrent spray nozzle scrubbing system designed to remove fluorine and hydrogen fluoride from the 3000 cfm of ventilation air passing through the Volatility Pilot Plant. A reduction of fluorine concentration from 1520 to <2 ppm during a total release of 68 lbs, and a reduction of hydrogen fluoride concentration from 4090 to <1 ppm during a total release of 200 lbs, will adequately protect the Fiberglas media filters. Six scrubbing states each containing four nozzle-throat spray units are needed with a 5 to 10% aqueous caustic potash recycle system pumping at a maximum rate of approximately 180 gal/min, with a range per nozzle from 3 to 7 gal/min. The scrubber will be 4 ft x 4 ft x approximately 25 ft, containing a deentrainment section of baffles and demister. The associated ventilation system hardware, services, and instrumentation requirements are given. (auth)
Date:
April 11, 1950
Creator:
Ruch, J B
System:
The UNT Digital Library
The Isotopes of Americium
Three new americium activities (Am{sup 238}?, Am{sup 243}, and Am{sup 244?}, the latter two formed by n,{gamma} reactions) are described and some additional information is given on previously reported americium isotopes.
Date:
April 11, 1950
Creator:
Street, K.; Ghiroso, A. & Seaborg, G. T.