Cryostat "UV" Relief Valve Selection and Process Flow (open access)

Cryostat "UV" Relief Valve Selection and Process Flow

This report describes the selection of the relief valves for the D-Zero cryostats. The selection was based on the flow requirements calculated in D-Zero engineering note 3740.214,224-EN-6 under fire conditions (1200 F, no vacuum) for the central cryostat; 264 SCFM. This value was calculated from section 5.3.5 of 'Pressure Relief Device Standards; S 1.3-Compressed Gas Storage Containers', published by the Compressed Gas Association, Inc. The flow calculated above is far greater than the required fire condition flow capacity of 264 SCFM. The improbable 70 F flow temperature value of 738 SCFM is still much greater than the required fire capacity. The flow capacity of the paralleled supplemental rupture disc is 2640 SCFM, independently greater than the fire condition flow requirement.
Date: August 11, 1987
Creator: Mulholland, G. T. & Wintercorn, S. J.